Home·TRANSGEAR POWER SYSTEMS PRIVATE LIMITED·Products·Dry Type(CRT) Transformers

Dry Type(CRT) Transformers

Certificates:ISO 9001/2008 certifiedISO 9001/2008 certified
TRANSGEAR POWER SYSTEMS PRIVATE LIMITEDBangalore, KA
Storefront
Anchored to the MCA registerCIN U31104KA2014PTC077245
Price on request. Ask the factory for a quote.
MOQ not stated Lead time on requestCurrency INR

Description

Dry Type Cast Resin and Vacuum Impregnated distribution transformer

Specifications

3 phase, 50 Hz, 11kV/0.433V Range: 25KVA to 2500KVA, Voltage class: Up to 33KV Off Load Tap Links / Changer to provide +5% to -5% taps in steps of 2.5% On Load Air / Vacuum Type Tap Changer to provide +5% to -15% taps in steps of 2.5% Class F/H insulated. Vector Group Dyn11. Continuous Duty. Copper / Aluminum Wound HV Side cable Box LV Side Cable Box / Bus Duct Painting: RAL 7032 (Siemens Grey) / As per requirement Standard Fittings as per IS/IEC standards Enclosure with IP 21 protection for Indoor and IP 43 protection for Outdoor Application

Features

  • Design conforms to IS 2026/11171, IEC 60076-11 and other International standards.
  • Designed for trouble-free performance
  • ISO 9001/2008 certified.
  • Low Partial Discharge (<10pC)
  • Energy efficient (Low power loss) and low noise
  • Designed to withstand electric impulses, thermal and dynamic stresses.
  • Compact in size.
  • Modern manufacturing techniques ensure cost effectiveness and reliability
  • Averts fire and prevents it from spreading.
  • Designed to meet customized specifications

Standard Accessories

  • Winding Temperature scanner with alarm and trip contacts
  • Remote tap changer control cubicle for OLTC transformer.

Optional Accessories

  • Neutral Current Transformer
  • Blowers and Exhaust Fans for Forced Cooling and enhanced capacity for transformer
  • Surge arrestors
  • Bi-Directional Rollers

Test Facilities

  • ALL ROUTINE TESTS AS PER IS 2026 & IS 1180 ARE PERFORMED IN HOUSE USING FULLY AUTOMATED TEST BENCHES & ADVANCED TESTING SOFTWARE.
  • Measurement of Winding Resistance.
  • Verification of Voltage Ratio.
  • Verification of Vector Group.
  • Measurement of No-Load Current & Losses (NLL).
  • Measurement of Impedance (Z) and Load Losses (LL).
  • Measurement of Insulation Resistance.
  • Power frequency / High Voltage test.
  • Induced over Voltage Test (IOVT)

Certificates

ISO 9001/2008 certified
ISO 9001/2008 certified

Reviews

Reviews here are order-verified. Only buyers who completed a delivered order can rate this supplier, so the first review appears after the first delivery on BharatSeal.

Questions & answers

Ask the supplier. Answers are visible to all buyers

No questions yet. Ask the first one: the supplier is notified and the answer is posted here for every buyer.

Know your supplier

TRANSGEAR POWER SYSTEMS PRIVATE LIMITED
Unverified<1 yr on BharatSealBangalore, Karnataka
Year founded
2008
Certifications
2

More from Transgear Power Systems